Shaanxi Qindiyuan Environmental Protection Equipment Co., Ltd.
leonleesale@aliyun.com 86--15389206502
Products
Products
Home > Products > Industrial Sensors‌ > 2-wire HART 7 Temperature Transmitters PR 6437A With RTD TC MV Inputs

2-wire HART 7 Temperature Transmitters PR 6437A With RTD TC MV Inputs

Product Details

Place of Origin: Denmark

Brand Name: PR

Certification: CO

Model Number: PR 6437A

Document: 6437v101_uk.pdf

Payment & Shipping Terms

Minimum Order Quantity: 1

Price: 170usd

Delivery Time: 5-7 work days

Payment Terms: T/T

Supply Ability: 99pcs 4-6 weeks

Chat now
Highlight:

HART 7 Temperature Transmitters

,

Temperature Transmitters PR 6437A

,

Sensor Redundancy PR 6437A

2-wire HART 7 Temperature Transmitters PR 6437A With RTD TC MV Inputs
PR 6437A 2-Wire HART 7 Temperature Transmitter
Product Overview

Advanced 2-wire HART 7 temperature transmitter supporting RTD, TC, potentiometer, linear resistance and bipolar mV inputs. Features single or true dual inputs with sensor redundancy and drift detection capabilities.

Environmental Conditions
Operating temperature -50°C to +85°C (standard) -40°C to +80°C (SIL)
Storage temperature -50°C to +85°C
Calibration temperature 23...25°C
Relative humidity < 99% RH (non-cond.)
Protection degree IP20
Mechanical Specifications
Dimensions (HxWxD) 109 x 23.5 x 104 mm
Weight (single input / dual input) 150 g / 160 g
Wire size 0.13...2.08 mm² AWG 26...14 stranded wire
DIN rail type DIN EN 60715/35 mm
Screw terminal torque 0.5 Nm
Vibration IEC 60068-2-6
2...25 Hz: ±1.6 mm
25...100 Hz: ±4 g
Common Specifications
Supply
Supply voltage 7.5*...48** VDC
Power dissipation, per channel ≤ 850 mW
Additional min. supply voltage when using test terminals 0.8 V
Min. load resistance at >37 V supply (Vsupply - 37) / 23 mA
Performance Characteristics
Isolation voltage, test / working 2.5 kVAC / 55 VAC
Response time 75 ms
Programmable damping 0...60 s
Polarity protection All inputs and outputs
Warm-up time < 5 min.
Start-up time < 2.75 s
Programming HART & PR 5909 Loop Link communications interface
Write protection Jumper or software
Signal / noise ratio > 60 dB
Long-term stability, better than ±0.05% of span / year (±0.18% of span / 5 years)
Signal dynamics, input 24 bit
Signal dynamics, output 18 bit
Effect of supply voltage change < 0.005% of span / VDC
Accuracy See manual for details
EMC immunity influence < ±0.1% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst < ±1%
Input Specifications
RTD Input
RTD type Pt10...10000, Ni10...10000, Cu5...1000
Basic accuracy, e.g. Pt100 ≤ ±0.04°C
Cable resistance per wire 50 Ω (max.)
Effect of sensor cable resistance (3-/4-wire) < 0.002 Ω / Ω
Sensor current < 0.15 mA
Sensor error detection None, Shorted, Broken, Shorted or Broken
TC Input
Thermocouple type B, E, J, K, L, N, R, S, T, U, W3, W5, LR
Basic accuracy, e.g. TC K ≤ ±0.25°C
Cold junction compensation (CJC) Constant, internal or external via a Pt100 or Ni100 sensor
Sensor error detection None, Shorted, Broken, Shorted or Broken
Linear Resistance Input
Measurement range / min. range (span) 0 Ω...100 kΩ / 25 Ω
Cable resistance per wire (max.) 50 Ω
Sensor current < 0.15 mA
Sensor error detection None, Broken
Potentiometer Input
Potentiometer min....max. 10 Ω...100 kΩ
Measurement range / min. range (span) 0...100% / 10%
Cable resistance per wire (max.) 50 Ω
Sensor current < 0.15 mA
Sensor error detection None, Shorted, Broken, Shorted or Broken
mV Input
Measurement range -800...+800 mV (bipolar) -100...1700 mV
Min. measurement range (span) 2.5 mV
Input resistance 10 MΩ
Sensor error detection None, Broken
Output Specifications
Normal range, programmable 3.8...20.5 / 20.5...3.8 mA
Extended range (output limits), programmable 3.5...23 / 23...3.5 mA
Basic accuracy ≤ ±1.6 μA (0.01% of full output span)
Updating time 10 ms
Load (@ current output) ≤ (Vsupply -7.5)/0.023 [Ω]
Load stability < 0.01% of span / 100 Ω
Sensor error indication Programmable 3.5…23 mA
NAMUR NE 43 Upscale/Downscale > 21 mA / < 3.6 mA
HART protocol revisions HART 7 and HART 5
Compliance & Approvals
Regulatory Compliance
EMC 2014/30/EU & UK SI 2016/1091 2014/30/EU
RoHS 2011/65/EU & UK SI 2012/3032
ATEX 2014/34/EU & UK SI 2016/1107
EAC TR-CU 020/2011
EAC Ex TR-CU 012/2011
International Approvals
ATEX DEKRA 18ATEX0135X
IECEx IECEx DEK. 16.0029X
CSA CSA 16.70066266
c FM us FM16US0287X / FM16CA0146X
INMETRO DEKRA 23.0002X
NEPSI GYJ23.1253X
EAC Ex EAEU KZ 7500361.01.01.08756
EU RO MR Type Approval MRA0000023
SIL SIL 2 / SIL 3 certified & fully assessed acc. to IEC 61508
Note: * / ** See manual for detailed specifications and operating conditions.