Shaanxi Qindiyuan Environmental Protection Equipment Co., Ltd.
leonleesale@aliyun.com 86--15389206502
Produk
Produk
Rumah > Produk > Signal Transmitter > PR 5131A 2 Wire Programmable Transmitter 3.75 kVAC Galvanic Isolation RTD TC mV Input

PR 5131A 2 Wire Programmable Transmitter 3.75 kVAC Galvanic Isolation RTD TC mV Input

Rincian produk

Tempat asal: Denmark

Nama merek: PR

Sertifikasi: CO

Nomor model: PR 5131A

Dokumen: 5131.pdf

Syarat Pembayaran & Pengiriman

Kuantitas min Order: 1

Harga: 150-250usd

Waktu pengiriman: 5-7 hari kerja

Syarat-syarat pembayaran: T/T

Menyediakan kemampuan: 99pcs 4-6 minggu

bicara sekarang
Menyoroti:

PR 5131A Programmable Transmitter

,

PR 5131A Programmable Transmitter

,

Programmable Transmitter 3.75 kVAC

Tipe tampilan:
LCD
ResponseTime:
≤ 1 detik
Nama Produk:
Pemancar Multifungsi
SignalType:
Analog/Digital
Tipe pemasangan:
Rel DIN / Pemasangan Panel
Peringkat perlindungan:
IP65
Fungsionalitas:
Multifungsi
Rentang keluaran:
4-20mA / 0-10V
bahan perumahan:
Paduan Aluminium
Catu daya:
24VDC
Rentang masukan:
0-10V / 4-20MA
Ketepatan:
±0,1%
Suhu pengoperasian:
-20°C hingga 70°C
Protokol Komunikasi:
HART / Modbus
Tipe tampilan:
LCD
ResponseTime:
≤ 1 detik
Nama Produk:
Pemancar Multifungsi
SignalType:
Analog/Digital
Tipe pemasangan:
Rel DIN / Pemasangan Panel
Peringkat perlindungan:
IP65
Fungsionalitas:
Multifungsi
Rentang keluaran:
4-20mA / 0-10V
bahan perumahan:
Paduan Aluminium
Catu daya:
24VDC
Rentang masukan:
0-10V / 4-20MA
Ketepatan:
±0,1%
Suhu pengoperasian:
-20°C hingga 70°C
Protokol Komunikasi:
HART / Modbus
PR 5131A 2 Wire Programmable Transmitter 3.75 kVAC Galvanic Isolation RTD TC mV Input
PR 5131A 2-Wire Programmable Transmitter

A versatile 2-wire programmable transmitter supporting multiple input types including RTD, TC, mV, linear resistance, mA, and V with 3.75 kVAC galvanic isolation and 4...20 mA loop output.

  • Input for RTD, TC, mV, linear resistance, mA, and V
  • 3.75 kVAC galvanic isolation
  • 4...20 mA loop output
  • 1- or 2-channel version available
  • DIN rail mounting
Environmental Conditions
Operating temperature-20°C to +60°C
Calibration temperature20...28°C
Relative humidity< 95% RH (non-condensing)
Protection degreeIP20
Mechanical Specifications
Dimensions (HxWxD)109 x 23.5 x 130 mm
Weight approx.195 g
DIN rail typeDIN EN 60715/35 mm
Wire size0.13...2.08 mm² AWG 26...14 stranded wire
Screw terminal torque0.5 Nm
Common Specifications
Supply
Supply voltage7.5...35 VDC
Fuse50 mA SB / 250 VAC
Isolation Voltage
Isolation voltage, test / working3.75 kVAC / 250 VAC
PELV/SELVIEC 61140
Response Time
Temperature input, programmable (0...90%, 100...10%)400 ms...60 s
mA / V input (programmable)250 ms...60 s
ProgrammingPR 5909 Loop Link communications interface
Signal / noise ratioMin. 60 dB (0...100 kHz)
Signal dynamics, input22 bit
Signal dynamics, output16 bit
Updating time115 ms (temperature input) 75 ms (mA / V / mV input)
Performance Characteristics
EMC immunity influence< ±0.5% of span
Extended EMC immunity: NAMUR NE21, A criterion, burst< ±1% of span
Effect of supply voltage change< 0.005% of span / VDC
Input Specifications
Common Input Specifications
Max. offset50% of selected max. value
RTD Input
RTD typePt100, Ni100, lin. R
Cable resistance per wire10 Ω (max.)
Sensor currentNom. 0.2 mA
Effect of sensor cable resistance (3-/4-wire)< 0.002 Ω / Ω
Sensor error detectionYes
TC Input
Thermocouple typeB, E, J, K, L, N, R, S, T, U, W3, W5, LR
Cold junction compensation (CJC)< ±1.0°C
Sensor error currentNom. 30 μA
Sensor error detectionYes
Current Input
Measurement range0...100 mA
Min. measurement range (span)4 mA
Input resistance: Supplied unitNom. 10 Ω + PTC 10 Ω
Input resistance: Non-supplied unitRSHUNT = ∞, VDROP < 6 V
mV Input
Measurement range-150...+150 mV
Voltage Input
Measurement range0...250 VDC
Min. measurement range (span)5 mV
Input resistanceNom. 10 MΩ (≤ 2.5 VDC) Nom. 5 MΩ (> 2.5 VDC)
Output Specifications
Current Output
Signal range4…20 mA
Min. signal range10 mA
Load (@ current output)≤ (Vsupply - 7.5) / 0.023 [Ω]
Load stability≤ 0.01% of span / 100 Ω
Current limit≤ 28 mA
Sensor error indicationProgrammable 3.5…23 mA
NAMUR NE43 Upscale/Downscale23 mA / 3.5 mA
of span= of the presently selected range
Compliance & Certifications
EMC2014/30/EU
LVD2014/35/EU
RoHS2011/65/EU
EACTR-CU 020/2011